upvote
That simply can not be true, or you could make more electrically efficient systems by just increasing the surface area of the condenser. That sort of efficiency increase alone should give you reason to suspect it.
reply
> They have a coating that can be applied to HVAC units which results in about a 40% improvement in energy efficiency.

Sorry to disappoint, but their coating will not do that.

As far as I can see, they've mixed some graphene into a corrosion protection coating. Then their marketing team abandoned reality and claimed 40% improvements in something.

Corrosion protection is important for extending service life of an HVAC unit, but the coating isn't going to increase efficiency by 40%, or at all. It's a film on top of the coils which technically reduces thermal performance, but the film is so small I guarantee this is negligible.

Maybe they're trying to claim that the graphene in the mix improves emissivity? You would achieve the same result by coating the coils with anything black, but that's a negligible factor.

Sorry to burst your bubble, but this company doesn't have anything that will change world energy consumption. It's a corrosion inhibitor with a little bit of graphene and a lot of marketing.

reply
Ya, I was thinking it’s maybe in comparison to a coating that doesn’t have graphene or something. If it was a real 40% efficiency gain, manufacturers would already be applying it.
reply
+1 I tried to skim through what they were measuring. My best guess was maybe the coating prevents grime/grease buildup so most of that was the difference between clean coils and dirty coils.
reply
exactly. show me independent studies of performance or this is just marketing garbage.
reply
Correct me if I'm wrong but as I understand it this doesn't mean 40% more efficient AC, it's only the heatsink being 40% more efficient at dissipating heat?
reply
I don't have details handy, but this is a little farther down on their website. There's also a chart of field study results farther down.

> 10-50% energy reduction measured across commercial HVAC, chillers and data centres.

reply
"40% more efficient A/C" is a way, way, way milder claim than "40% better heat sink" so I would assume that they're making the former claim.
reply
No it isn’t.

If the claim is 40% more efficient AC, that’s the whole system.

If it were only for, say, the heat sink component, thats only one component.

You see how one component being more efficient contributes only a fraction to the total system?

reply
You can make a system suck 40% less energy by improving one component enough to cross some threshold that makes whatever the energy suck is happen less (e.g. the difference between zero and some insulation on a fridge). That's easy.

Improving the heat transfer of a heat sink with a surface coating is hard (for reasonable definitions of "heat sink" and "surface coating") because you run right into physics.

reply
Really? I guess making a heatsink dissipate 40% more heat is great for lots of applications (and hard), but it shouldn't translate to great gains in AC efficiency, right?
reply
This is great, but more solar PV installs would help too -- they should pay for themselves in a reasonable amount of time for those with high electrical costs.
reply
There’s a reason infomercials use that sort of language. It’s like when HN users are disappointed that the average of all human English language produces substandard (for them) AI-isms in the output.

Maybe they did focus group tests that showed that name got them the attention they needed in that market.

reply
Painting surfaces for heat transfer is a 200yo trick. It's not worth 40%. It's more like +10%/-20% if you're being optimistic and using super modern engineered materials.

They must be making some weird marketing truck where they've set up some special situation where 10% improvement results in 4x that reduction in energy usage some other way For example in a heating context it's really easy to imagine how a 10% improvement to a heat pump could result in it kicking on the resistive heating much less in some climates for an overall 40% reduction in energy for the same set point.

If real world performance were anywhere near claimed without unacceptable tradeoffs (falls off if you look at it funny and then the dust gives you an incurable disease) and if you it would already be everywhere. Even if it cost as much as upsizing the hardware you'd see it space constrained applications.

15yr ago everyone was making the same silver bullet claims about ERV/HRV and it turned out those only really move the needle for very specific climates and building uses but the sellers are laughing all the way to the bank because the various codes and green this and that incentives that they got written into draw no such distinction.

So yeah, color me skeptical.

reply
deleted
reply